How to use the voltage drop calculator
- Choose copper or aluminum and the wire size in AWG or mm².
- Pick DC / single-phase or three-phase, then enter the supply voltage and the load current.
- Enter the one-way length of the run. Read the drop, the voltage left at the load and the smallest wire that keeps the drop at 3% or less.
Voltage drop formula
Vdrop = k × I × L × ρ ÷ A, k = 2 (DC, 1-phase) or √3 (3-phase)
ρ is the resistivity (copper 1.724 × 10⁻⁸ Ω·m, aluminum 2.82 × 10⁻⁸ Ω·m at 20 °C) and A is the cross-section area. Example: 15 A through 100 ft (30.48 m) of 12 AWG copper (3.31 mm²) on 120 V: 2 × 15 × 30.48 × 1.724 × 10⁻⁸ ÷ 3.31 × 10⁻⁶ = 4.76 V, a 3.97% drop. Going up to 10 AWG brings it to 2.5%.
Look up any size in the wire gauge chart, or work out the current a load draws with the watts to amps calculator.
Frequently asked questions
For DC and single-phase AC: Vdrop = 2 × L × I × R, where L is the one-way length, I the current and R the wire's resistance per unit length (the 2 covers the run out and back). For three-phase: Vdrop = √3 × L × I × R. The percentage is Vdrop ÷ supply voltage × 100.
The US National Electrical Code recommends (in an informational note) no more than 3% on a branch circuit and 5% in total from the service to the outlet. The UK's BS 7671 allows 3% for lighting and 5% for other uses. Low-voltage DC systems such as 12 V solar or automotive wiring often aim for 2–3%, because a small drop is a big share of 12 V.
Use a thicker wire (a lower AWG number or larger mm²), shorten the run, or raise the system voltage: the same power at 240 V draws half the current of 120 V and has a quarter of the percentage drop. Copper drops less than aluminium of the same size.
Enter the distance from the supply to the load. The calculator doubles it for DC and single-phase, because current flows out on one conductor and back on the other.
It uses the DC resistance of the conductor at 20 °C. Real wires running warm have about 10–20% more resistance, and large AC cables add some reactance, so treat the result as a close estimate and add a margin. For code-compliant designs, follow your local electrical code's tables.