kW to kVA formula
S(kVA) = P(kW) ÷ PF
Example: A 40 kW load with a power factor of 0.8 needs a 40 ÷ 0.8 = 50 kVA supply.
Generators and transformers are rated in kVA; divide the load's real power by its power factor.
How to use the calculator
- Choose the conversion, such as watts to amps or kVA to kW.
- Pick DC, AC single-phase or AC three-phase. For three-phase, enter the line-to-line voltage.
- Enter the values asked for. For AC, set the power factor: 1 for heaters and lights, about 0.8 for motors.
Electrical power formulas
| Find | DC | AC single-phase | AC three-phase |
|---|---|---|---|
| Watts P | V × I | PF × V × I | √3 × PF × V × I |
| Amps I | P ÷ V | P ÷ (PF × V) | P ÷ (√3 × PF × V) |
| Volts V | P ÷ I | P ÷ (PF × I) | P ÷ (√3 × PF × I) |
| VA S | V × I | V × I | √3 × V × I |
All conversions
Need resistance too? Use the Ohm's law calculator. Working out running costs? Try the electricity cost calculator.
Frequently asked questions
Generators and transformers are rated in kVA; divide the load's real power by its power factor. The formula is S(kVA) = P(kW) ÷ PF. A 40 kW load with a power factor of 0.8 needs a 40 ÷ 0.8 = 50 kVA supply.
The ratio of real power (watts) to apparent power (volt-amps) in an AC circuit, between 0 and 1. Resistive loads like heaters and kettles have a PF of 1. Motors, compressors and older fluorescent ballasts are often 0.7 to 0.9. Modern electronics with power-factor correction are usually above 0.95.
For three-phase supplies, common in commercial buildings and for large motors. Enter the line-to-line voltage, for example 400 V in Europe or 208 V or 480 V in the US. Three-phase formulas include √3 ≈ 1.732.
Watts measure real power that does work. Volt-amps (VA) measure apparent power, simply volts × amps. They're equal when the power factor is 1; otherwise watts = VA × PF. Wiring, fuses and transformers must carry the full VA.