kVA to Amps formula
Single-phase: I = 1,000 × S(kVA) ÷ V
Three-phase: I = 1,000 × S ÷ (√3 × V)
Example: A 50 kVA three-phase transformer at 400 V supplies up to 50,000 ÷ (1.732 × 400) = 72.2 A.
kVA is apparent power, so no power factor is needed.
How to use the calculator
- Choose the conversion, such as watts to amps or kVA to kW.
- Pick DC, AC single-phase or AC three-phase. For three-phase, enter the line-to-line voltage.
- Enter the values asked for. For AC, set the power factor: 1 for heaters and lights, about 0.8 for motors.
Electrical power formulas
| Find | DC | AC single-phase | AC three-phase |
|---|---|---|---|
| Watts P | V × I | PF × V × I | √3 × PF × V × I |
| Amps I | P ÷ V | P ÷ (PF × V) | P ÷ (√3 × PF × V) |
| Volts V | P ÷ I | P ÷ (PF × I) | P ÷ (√3 × PF × I) |
| VA S | V × I | V × I | √3 × V × I |
All conversions
Need resistance too? Use the Ohm's law calculator. Working out running costs? Try the electricity cost calculator.
Frequently asked questions
kVA is apparent power, so no power factor is needed. The formula is Single-phase: I = 1,000 × S(kVA) ÷ V; Three-phase: I = 1,000 × S ÷ (√3 × V). A 50 kVA three-phase transformer at 400 V supplies up to 50,000 ÷ (1.732 × 400) = 72.2 A.
The ratio of real power (watts) to apparent power (volt-amps) in an AC circuit, between 0 and 1. Resistive loads like heaters and kettles have a PF of 1. Motors, compressors and older fluorescent ballasts are often 0.7 to 0.9. Modern electronics with power-factor correction are usually above 0.95.
For three-phase supplies, common in commercial buildings and for large motors. Enter the line-to-line voltage, for example 400 V in Europe or 208 V or 480 V in the US. Three-phase formulas include √3 ≈ 1.732.
Watts measure real power that does work. Volt-amps (VA) measure apparent power, simply volts × amps. They're equal when the power factor is 1; otherwise watts = VA × PF. Wiring, fuses and transformers must carry the full VA.