How to use the power factor calculator
- Enter real power and apparent power, or switch tabs and enter the measured volts, amps and watts.
- Read the power factor, the phase angle and the reactive power, with the power triangle.
- Set a target PF to see the capacitor bank (kVAR) needed to correct it, and the reduction in current.
Power factor formulas
PF = P ÷ S = cos φ S² = P² + Q² Q = √(S² − P²)
Qc = P × (tan φ₁ − tan φ₂) C = Qc ÷ (2π f V²)
Example: a 40 kW load drawing 50 kVA has PF = 40 ÷ 50 = 0.80 (φ = 36.87°) and Q = 30 kVAR. To reach 0.95 (φ = 18.19°) you need Qc = 40 × (0.75 − 0.329) = 16.85 kVAR, and the apparent power drops to 42.1 kVA: about 16% less current.
Convert between kW, kVA and amps with the kW to kVA calculator and the electrical power calculator.
Frequently asked questions
Power factor (PF) is real power divided by apparent power: PF = P ÷ S = watts ÷ volt-amps. It runs from 0 to 1. A PF of 1 means all the current does useful work; a lower PF means extra current flows back and forth, heating cables and transformers without doing work.
Measure the real power with a wattmeter and the voltage and current with a meter. For single-phase, PF = P ÷ (V × I); for three-phase, PF = P ÷ (√3 × V × I). A motor drawing 1,800 W at 230 V and 9.8 A has a PF of 1,800 ÷ 2,254 = 0.80.
Above 0.95 is considered good. Many utilities charge commercial and industrial customers a penalty below 0.90 or 0.85. Lightly loaded induction motors can fall to 0.5 or less.
Inductive loads like motors draw lagging reactive power. A capacitor supplies leading reactive power that cancels part of it, so less current is drawn from the supply. The capacitor size is Qc = P × (tan φ₁ − tan φ₂), where φ₁ and φ₂ are the angles before and after correction.
kW is real power (does work), kVAR is reactive power (sustains magnetic and electric fields), and kVA is apparent power, the combination: kVA² = kW² + kVAR². They form the power triangle shown above.